Furring strips are thin wood or metal strips fastened over studs, masonry or sheathing to give a flat nailing surface or an air space for a finish. Under 2021 IRC Section R702.3.2, wood furring behind drywall must be at least 1x2 nominal over framing no more than 24 inches on center.

A furring strip, often called strapping, is not a structural member. It does not carry floor or roof loads. Its job is to hold a finish: drywall, paneling, shingle siding, stucco lath or cladding over rigid foam. Because each finish has its own section in the 2021 International Residential Code (IRC), the size and spacing rules for furring are spread across Chapters 3 and 7. This page pulls them together.

Key facts

  • Wood furring strips supporting gypsum board must be not less than 1-inch by 2-inch nominal and may only be used over solid backing or framing spaced not more than 24 inches on center (2021 IRC Section R702.3.2).
  • Furring under interior wood shakes and shingles must be 1x2 or 1x3, spaced at the desired exposure and nailed through the wall material into the studs (2021 IRC Section R702.6.2).
  • Horizontal furring under exterior wood shakes and shingles must be 1x3 or 1x4, fastened to the studs with minimum 7d or 8d box nails (2021 IRC Section R703.6.1).
  • Furring behind stucco lath must be at least 1x2 wood, 3/4-inch metal channel or self-furring lath, spaced not more than 24 inches on center (2021 IRC Section R703.7.1.1).
  • Horizontal wood furring over foam sheathing must be preservative-treated or naturally durable, with corrosion-resistant fasteners (2021 IRC Section R703.15.2).
  • Wood furring fixed directly to the inside of a below-grade concrete or masonry wall must be treated or naturally durable unless an approved vapor retarder separates them (2021 IRC Section R317.1, item 7).

What are furring strips used for?

Furring strips give a finish something straight and solid to fasten to when the surface behind it cannot do that job on its own. The common uses on a house are:

  • Flattening a wall or ceiling. Strips shimmed over uneven joists or studs give drywall a true plane.
  • Covering masonry and concrete. Strips fastened to a block or poured basement wall carry drywall or paneling without building a full stud wall.
  • Spacing for shingles. Horizontal strips set the course spacing for wood shakes and shingles.
  • Holding stucco lath off the substrate so the plaster can key into the lath.
  • Fastening cladding over rigid foam. Strips screwed or nailed through foam into the studs carry the siding weight and leave a drainage gap.

Common lumber sizes are 1x2, 1x3 and 1x4, plus 2x2 and 2x furring where a deeper nailing base is needed. Nominal and actual sizes differ, so check dimensional lumber sizes before you work out a wall thickness.

Furring strips for drywall: what size and spacing?

Furring strips under drywall must be at least 1-inch by 2-inch nominal and may only go over solid backing or framing at no more than 24 inches on center (2021 IRC Section R702.3.2). The same section requires any other wood framing that supports gypsum board to be at least 2 inches nominal in its least dimension.

In practice, the strips run across the joists or studs and the drywall is fastened to the strips. The fastener spacing for the board itself comes from Table R702.3.5, covered in drywall screw spacing. Board thickness and the maximum framing spacing for each thickness are in drywall thickness.

Two practical points the code does not spell out:

  • Lay the strips out so every drywall edge and end lands on a strip.
  • Fasten each strip into every joist or stud it crosses, not only into the substrate between them.

How far apart should furring strips be?

There is no single spacing: it depends on the finish, with 24 inches on center as the upper limit behind stucco and over foam sheathing. The table below lists each rule in the 2021 IRC that sets furring size or spacing.

2021 IRC furring strip size and spacing by use (Sections R702.3.2, R702.6.2, R703.6.1, R703.7.1.1 and Table R703.15.2 note f).

UseMinimum furring sizeMaximum spacingFastening rule
Behind gypsum board (drywall)1x2 nominal woodOver framing not more than 24" o.c.Over solid backing or framing
Interior wood shakes and shingles1x2 or 1x3Equal to the desired exposureNailed through wall material into studs
Exterior wood shakes and shingles (horizontal strips)1x3 or 1x4Equal to actual weather exposure, not over Table R703.6.1Minimum 7d or 8d box nails into studs
Stucco lath1x2 wood, 3/4" metal channel or self-furring lath24" o.c.Into framing members over wood or steel framing
Cladding over foam sheathing1x wood (2x where note d applies)24" o.c.Per Table R703.15.2

Furring strips for siding and shingles

For exterior wood shakes and shingles, Section R703.6.1 allows application over nominal 1/2-inch wood-based sheathing, or to furring strips over 1/2-inch nominal nonwood sheathing. Horizontal strips are 1x3 or 1x4, nailed to the studs with minimum 7d or 8d box nails and spaced to match the actual weather exposure of the shingles. That exposure may not exceed Table R703.6.1.

Where the water-resistive barrier is nonpermeable, the same section requires vertical strips first, over the barrier, with the horizontal strips fastened to the vertical ones. The shingle fasteners must penetrate the sheathing or furring strips by not less than 1/2 inch (Section R703.6.3).

For vinyl siding, Section R703.11.1.2 requires fasteners to penetrate building framing, with a total penetration into sheathing, furring and framing of at least 1-1/4 inches, unless the manufacturer's instructions and a test report say otherwise. See vinyl siding installation for the rest of that section.

Furring strips behind stucco

Stucco furring must be at least 1x2 wood, 3/4-inch metal channel or self-furring lath, spaced not more than 24 inches on center and fastened into the framing (2021 IRC Section R703.7.1.1). The furring must also follow ASTM C1063. Lath is attached to the framing or furring under Section R703.7.1, but where the stucco is serving as wall bracing the lath must go directly to framing, not to furring. The full lath and plaster sequence is in stucco lath.

Furring strips over foam sheathing

When siding goes over rigid foam with wood furring, Section R703.15.2 sends you to Table R703.15.2 for the furring fasteners. The table gives the maximum foam thickness for each fastener, fastener spacing and siding weight. Its notes add:

  • Wood framing and furring must be spruce-pine-fir or a species with a specific gravity of 0.42 or more (note a).
  • Where the cladding fastener needs more than 3/4 inch and not more than 1-1/2 inches of penetration into wood, use minimum 2x furring or an approved design (note d).
  • Furring is spaced not more than 24 inches on center. Vertical furring sits over the studs. In a horizontal orientation, the 8-inch and 12-inch fastener spacings are achieved with two fasteners into studs at 16 and 24 inches on center (note f).

Horizontal wood furring over foam must be preservative-treated or naturally durable wood, with corrosion-resistant fasteners.

2021 IRC Table R703.15.2: minimum 1x wood furring on minimum 2x wood studs, 0.131-inch diameter nail, 1-1/4 inch minimum penetration into framing. Values are the maximum foam sheathing thickness in inches. DR = design required.

Fastener spacing in furring16" o.c. furring, 3 psf siding16" o.c. furring, 11 psf16" o.c. furring, 15 psf24" o.c. furring, 3 psf24" o.c. furring, 11 psf24" o.c. furring, 15 psf
8"4.002.451.754.001.601.10
12"4.001.601.104.000.950.55
16"4.001.100.703.050.60DR

Heavier siding, other fasteners (0.162-inch nails, No. 10 wood screws, 1/4-inch lag screws) and the 18 and 25 psf columns are in the full table. Where the cladding manufacturer has approved instructions for use over foam, those govern (Section R703.15, exception 1). Steel studs use Table R703.16.2 instead.

Do furring strips on concrete need to be pressure treated?

Yes, on the inside of a below-grade concrete or masonry exterior wall, unless an approved vapor retarder is installed between the wall and the wood (2021 IRC Section R317.1, item 7). The treated or naturally durable requirement covers furring strips and any other wood framing attached directly to that wall.

Above grade, or where the furring sits on a vapor retarder, untreated strips are allowed by that item. The treatment categories and where each applies are in pressure treated lumber for ground contact. If you are deciding between furring and a full stud wall in a basement, how to frame a basement wall compares the two.

Furring strips on a framing plan

Furring is a finish detail, so it usually appears on wall sections and finish schedules rather than on a floor or roof framing plan. A note such as 1x3 FURRING @ 16" O.C. OVER CMU, TREATED on the wall section tells the builder the size, spacing and treatment in one line. The stud spacing you choose for the frame sets where vertical furring lands.

The adopted code edition and local amendments govern, and cladding, foam and fastener manufacturers' instructions apply where the code points to them. For the full code text, the International Code Council publishes the 2021 IRC.

Summary

Furring strips are nonstructural strips that give a finish a flat, fastenable surface. Behind drywall they must be at least 1x2 nominal over framing no more than 24 inches on center (R702.3.2). Behind stucco and over foam sheathing they are capped at 24 inches on center (R703.7.1.1, Table R703.15.2), and under wood shingles they are spaced to the exposure (R702.6.2, R703.6.1). On the inside of below-grade concrete or masonry they must be treated or naturally durable unless a vapor retarder separates them (R317.1).

Framing Plan is a preliminary drawing aid that draws joist layouts, beams and openings and exports PNG, PDF and DXF. It does not detail furring or check code, and the editor works in millimeters, so add furring notes to your wall sections. Open the framing studio to lay out the frame the furring will sit on.